Yuanheng Liye Dual-Channel Online Calibration Smoke Chamber
The author: Release time:2026-04-06 views:1302




ATTRIBUTE

● tandard Smoke Chamber: The equipment has dimensions of approximately 3100 mm (L) × 700 mm (W) × 930 mm (H).Equipped with a DC fan speed control, the air velocity in the measurement area is adjustable within the range of 0–2 m/s.
An aerosol generator (including 250 mL liquid paraffin) is provided. The test smoke is light paraffin, with a smoke particle size distribution between 0.5 μm and 1.0 μm. The test smoke exhibits reproducibility and stability in terms of particle distribution, particle size, particle structure, and optical characteristics.

● Optical Densitometer: The optical wavelength is within the range of 880 nm to 950 nm.

● Calibration Method: The product is transferred from the assembly station to the smoke calibration station via a belt conveyor. It is manually picked and placed into the test position online. After calibration, the product is manually picked and placed for transfer to the next station.FIRE ALARM TEST EQUIPMENTS Dedicated to providing advanced fire alarm detector testing equipment for China and the world, making the world fire-free.
ACTION AND INTEGRITY Yuanheng Liye Dual-Channel Online Calibration Smoke Chamber

● Smoke Generation Device: An aerosol generator is used,which automatically recognizes and adjusts the concentration.

● Smoke Sampling in Calibration Chamber: An optical densitometer and a scatterer are used to monitor the smoke concentration inside the chamber.

● Number of Calibration Positions: Two calibration positions on each side (one active and one standby), used alternately. Each calibration position accommodates three products.

● Calibration Cycle: 4 units per side per 10 seconds. The calibration time for the alarm itself shall not exceed 2 seconds.
The throughput is 10,000 units per day based on an 8-hour shift. A communication protocol shall be provided for the user to develop the calibration software.

● Control Accuracy: ±0.015 dB/m
 